072419-senergy-masterspec



Copyright 2016 by The American Institute of Architects (AIA)

This Product MasterSpec Section modifies the original MasterSpec text and does not include the full content of the original MasterSpec Section.

Revisions made to the original MasterSpec text are made solely by the Licensee and are not endorsed by, or representative of the opinions of, Deltek or The American Institute of Architects (AIA). Neither AIA nor Deltek are liable in any way for such revisions or for the use of this Product MasterSpec Section by any end user. A qualified design professional should review and edit the document to suit project requirements.

For more information, contact BASF Corporation, 889 Valley Park Dr., Shakopp, MN 55379; Phone: (800) 243-6739; Website: senergy.; Email: basfbscst@.

For information about MasterSpec, contact Deltek at (800) 424-5080 or visit .

SECTION 072419 - WATER-DRAINAGE EXTERIOR INSULATION AND FINISH SYSTEM (EIFS)

TIPS:

To view non-printing Editor's Notes that provide guidance for editing, click on MasterWorks/Single-File Formatting/Toggle/Editor's Notes.

To read detailed research, technical information about products and materials, and coordination checklists, click on MasterWorks/Supporting Information.

Access Product MasterSpec Sections:

Revise this Section by deleting and inserting text to meet Project-specific requirements.

1. RELATED DOCUMENTS

Retain or delete this article in all Sections of Project Manual.

A.

2. SUMMARY

A. Section Includes:

1. EIFS-clad drainage-wall assemblies that are field applied over substrate.

Retain subparagraph below for water-resistive barrier coatings specified in this Section.

2.

B. Related Requirements:

Retain subparagraphs below to cross-reference requirements Contractor might expect to find in this Section but are specified in other Sections.

1.

Coordinate Section 072726 "Fluid-Applied Membrane Air Barriers" when specifying "MasterProtect" air- and water-barrier products. Other products specified in Section 072726 may not be used behind EIFS.

2.

3. Section 079200 "Joint Sealants" for sealing joints in EIFS with elastomeric joint sealants and for perimeter joints between system and other materials.

3. DEFINITIONS

Retain terms that remain after this Section has been edited for a project.

A.

B. EIFS: Exterior insulation and finish system(s).

C. IBC: International Building Code.

4. PREINSTALLATION MEETINGS

Retain "Preinstallation Conference" Paragraph below if Work of this Section is extensive or complex enough to justify a conference.

A.

If needed, insert list of conference participants not mentioned in Section 013100 "Project Management and Coordination."

5.

A. Product Data: For each EIFS component, trim, and accessory, including air/water-resistive barrier coatings.

B. Sustainable Design Submittals:

"Product Data" Subparagraph below applies to LEED 2009 NC, CI, and CS; LEED v4; IgCC; ASHRAE 189.1; and Green Globes. Coordinate with requirements for adhesives.

1.

"Laboratory Test Reports" Subparagraph below applies to LEED 2009 for Schools, LEED v4, IgCC, ASHRAE 189.1, and Green Globes. Coordinate with requirements for adhesives.

2.

"Product Data" Subparagraph below applies to LEED 2009 NC, CI, and CS; LEED v4; IgCC; ASHRAE 189.1; and Green Globes. Coordinate with requirements for coatings.

3.

"Laboratory Test Reports" Subparagraph below applies to LEED 2009 for Schools, LEED v4, IgCC, ASHRAE 189.1, and Green Globes. Coordinate with requirements for coatings.

4.

Retain "Samples" Paragraph below for single-stage Samples, with a subordinate list if applicable. Retain "Samples for Initial Selection" and "Samples for Verification" paragraphs for two-stage Samples.

C.

D. Samples for Initial Selection: For each type of finish-coat color and texture indicated.

1. Include similar Samples of exposed accessories involving color selection.

E. Samples for Verification: 6 inch- (150 mm-) square panels for each type of finish-coat color and texture indicated, prepared using same tools and techniques intended for actual work, including [custom trim, each profile,] [and] [an aesthetic reveal].

Retain subparagraph below for items directly associated with EIFS that are specified in this Section.

1.

6. INFORMATIONAL SUBMITTALS

Coordinate "Qualification Data" Paragraph below with qualification requirements in Section 014000 "Quality Requirements" and as may be supplemented in "Quality Assurance" Article.

A.

B. Manufacturer Certificates: Signed by EIFS manufacturer, certifying the following:

1. EIFS complies with requirements.

2. Substrates to which EIFS is indicated to be attached are acceptable to EIFS manufacturer.

3. Accessory products installed with EIFS, including [joint sealants,] [flashing,] [water-resistive barrier coatings,] [trim,] whether or not furnished by EIFS manufacturer and whether or not specified in this Section, are acceptable to EIFS manufacturer.

Retain "Product Bulletins" Paragraph below to require submittal of material or product certificates from manufacturers. Delete option if adhesive/base coats and finish coats are factory-mixed formulations and require only added water or are usable straight from container.

C.

D. Product Evaluation Reports: For each EIFS assembly and component, including air/water-resistive barrier coatings, for tests performed by a qualified testing agency.

Retain "Field quality-control reports" Paragraph below if Contractor is responsible for field quality-control testing. Testing may be required in addition to Special Inspections, to suit Project.

E.

F. Sample Warranty: For manufacturer's warranty.

7. CLOSEOUT SUBMITTALS

A. Maintenance Data: For EIFS to include in maintenance manuals.

8. QUALITY ASSURANCE

Retain "Installer Qualifications" Paragraph below if requirements in Section 014000 "Quality Requirements" are insufficient. Revise if installers are qualified by a means other than certification. Verify requirements of authorities having jurisdiction.

A.

B. Mockups: Build mockups to verify selections made under Sample submittals, to demonstrate aesthetic effects, and to set quality standards for fabrication and installation.

Indicate portion of wall represented by mockup on Drawings or draw mockup as separate element.

1.

2. Approval of mockups does not constitute approval of deviations from the Contract Documents contained in mockups unless Architect specifically approves such deviations in writing.

Retain subparagraph below if the intention is to make an exception to the default requirement in Section 014000 "Quality Requirements" for demolishing and removing mockups.

3.

9. DELIVERY, STORAGE, AND HANDLING

A. Deliver materials in original, unopened packages with manufacturers' labels intact and clearly identifying products.

B. Store materials in cool, dry place protected from freezing. Store at no less than 40 deg F (4.4 deg C).

1. Stack insulation board flat and off the ground.

Retain first subparagraph below for BASF's "Max Flash."

2.

3. Protect foam-plastic insulation against ignition and direct sunlight at all times.

4. Complete installation and concealment of plastic materials as rapidly as possible in each area of construction.

10. FIELD CONDITIONS

Weather and ambient conditions may affect drying and curing time and appearance.

A.

1. Proceed with installation of adhesives or coatings only when ambient temperatures have remained, or are forecast to remain, above 40 deg F (4.4 deg C) for a minimum of 24 hours before, during, and after application. Refer to manufacturer's written instructions for temperature limitations for specialty finish products. Do not apply EIFS adhesives or coatings during rainfall or to frozen or wet surfaces.

11. WARRANTY

When warranties are required, verify with Owner's counsel that warranties stated in this article are not less than remedies available to Owner under prevailing local laws.

A.

Verify available warranties and warranty periods for EIFS.

1.

PRODUCTS

Manufacturers and products listed in SpecAgent and MasterWorks Paragraph Builder are neither recommended nor endorsed by the AIA or Deltek. Before inserting names, verify that manufacturers and products listed there comply with requirements retained or revised in descriptions and are both available and suitable for the intended applications. For definitions of terms and requirements for Contractor's product selection, see Section 016000 "Product Requirements."

1.

Retain "Basis-of-Design Product" Paragraph and list of manufacturers below to require a specific product or a comparable product from manufacturers listed.

A.

1. Acrocrete; BASF Corp.

2. Finestone; BASF Corp.

3. ................
................