5. PHYSICAL CHARACTERISTICS



SPECIFICATIONS

For 2 ply, 3ply, and 4ply

DISPOSABLE PANEL FILTERS

INTERNAL WIRE FRAME TYPE

U.L. CLASS I & II

1. SCOPE

The 2 ply TRI-DEK 3/67 multi-graduated panel and link filters that are used as prefilters and final filters in air-conditioning, heating and ventilation systems.

2. PURPOSE

Establish performance criteria, and to identify physical properties of TRI-DEK 2 PLY PANELS AND LINKS that are pertinent and necessary for proper filter performance.

3. PERFORMANCE CRITERIA

3.1 The manufacturer shall have a representative sample of the product requested ` in the bid solicitation tested by an independent, commercially operated test laboratory approved by the purchaser. The independent test laboratory shall fully test one (1) representative filter purchased from the open market to ASHRAE Standard 52-76. The test must represent current production.

3.2 The resulting performance data shall be used to meet the following (3.2.2) Performance Requirements.

`

3.2.1

Nominal Filter Size 24 x 24 x 1

3.2.2

Performance Requirements

Maximum Initial Resistance 225 F.P.M. .10” W.G.

300 F.P.M. .15” W.G.

375 F.P.M. .20” W.G.

Final Resistance 1.0” W.G.

Min. Initial Atmospheric Dust Spot Efficiency < 20.0 %

Min. Average Atmospheric Dust Spot Efficiency < 20.0 %

Min. Average Atmospheric Dust Weight Arrestance 89.0 %

ASHRAE Dust Holding Capacity 225 Grams

4. BID ENCLOSURES

The following items must be part of the bid proposal. Failure to comply will cause

rejection of bids without recourse.

4.1 One (1) independent laboratory test report showing performance results when

tested to ASHRAE Standard 52-76. Permission shall be granted by the bidder to verbally verify the performance results with the independent laboratory that performed the test.

4.2 A product sample.

5. PHYSICAL CHARACTERISTICS

TRI-DEK 2 ply panel and link filters are constructed of a multi-graduated laminant of

variable denier synthetic fibers, permanently bonded together during manufacture. The upstream side of TRI-DEK panel and link filters are constructed of a heavy weight single denier polyester and the downstream layer is composed of a needled, all-polyester media that has dual directional strength, insuring filter integrity as it becomes loaded.

Additionally, all TRI-DEK panel and link filters are available treated with AEGIS brand Antimicrobial System.

Each panel or link shall have an inner hard-drawn wire frame, heat sealed between the two plys; with cross braces as necessary. After heat sealing, each panel or link shall have a minimum of 1/2” selvaged edge guaranteeing positive seal around the periphery of the filter.

TRI-DEK 2 ply panels and links are U.L. Class I and U.L. Class II listed and approved per U.L. Standard 900.

6. PACKAGING AND IDENTIFICATION

6.1 Shipping containers shall be marked with the following:

6.1.1 The name or trademark of the product.

6.1.2 The nominal size of the filter.

6.1.3 Name of manufacturer.

SPECIFICATIONS

DISPOSABLE PANEL FILTERS

INTERNAL WIRE FRAME TYPE

U.L. CLASS I & II

1. SCOPE

The 3 ply TRI-DEK 15/40 multi-graduated panel and link filters that are used as prefilters and final filters in air-conditioning, heating and ventilation systems.

2. PURPOSE

Establish performance criteria, and to identify physical properties of TRI-DEK 3 PLY PANELS AND LINKS that are pertinent and necessary for proper filter performance.

3. PERFORMANCE CRITERIA

1. The manufacturer shall have a representative sample of the product requested

in the bid solicitation tested by an independent, commercially operated test laboratory approved by the purchaser. The independent test laboratory shall fully test one (1) representative filter purchased from the open market to ASHRAE Standard 52.2 be included. The test must represent current production.

Note: An equivalent 52.1 or 52-76 test showing equal to or greater than fractional efficiencies as in section 3.2.2 will be accepted, these particle penetration numbers must be provided by an independent laboratory and product must be purchased from the open market with no exception. The test must represent current production.

3.2 The resulting performance data shall be used to meet the following (3.2.2) Performance Requirements.

3.2.1

Nominal Filter Size 24 x 24 x1

3.2.2

Performance Requirements

Maximum Initial Resistance 984 CFM .18” W.G.

1476 CFM .31”W.G.

1968 CFM .48”W.G.

2460 CFM .67”W.G.

Final Resistance 1.0” W.G.

Minimum Efficiency Rating 10 Rating

4. BID ENCLOSURES

The following items must be part of the bid proposal. Failure to comply will cause

rejection of bids without recourse.

4.1 One (1) independent laboratory test report showing performance results when

tested to ASHRAE Standard 52.2. Permission shall be granted by the bidder to verbally verify the performance results with the independent laboratory that performed the test.

4.2 A product sample.

5. PHYSICAL CHARACTERISTICS

TRI-DEK panel and link filters are constructed of 3 ply pre-crimped, multi-graduated denier fibers, permanently bonded together during manufacture to provide progressive filtration; large particles are strained from the air stream on the air entering side and progressively smaller particles throughout successive plys. the pre-crimped fibers employed in the 3 PLY TRI-DEK form millions of intersticed funnel shaped traps to arrest and permanently retain, in depth, solid particulate materials in proportion to their micron size, without interrupting uniform air flow.

* No Dyes are to be used in the media, this is to insure the product is environmentally friendly.

At manufacture, the first 2 plys, are permanently bonded together thereby providing a progressive density product in a single fabric. Individual plys laminated together are not acceptable, as mechanical bonding adversely affects air flow resistance, and shortens filter life. A wet tackifier must be applied between the last two plys of media to assist in retaining particles captured by the fibers. The tackifier must be non-toxic, non-allergenic material and, applied to the media at the time of manufacture.

Each panel or link shall have an inner hard-drawn wire frame, heat sealed between the two plys; with cross braces as necessary. After heat sealing, each panel or link shall have a minimum of 1/2” selvaged edge guaranteeing positive seal around the periphery of the filter.

TRI-DEK 3 ply panels and links are U.L. Class I and U.L. Class II listed and approved per U.L. Standard 900.

Additionally, all TRI-DEK panel and link filters are available treated with AEGIS brand Antimicrobial System.

6. PACKAGING AND IDENTIFICATION

6.1 Shipping containers shall be marked with the following:

6.1.1 The name or trademark of the product.

6.1.2 The nominal size of the filter.

3. Name of manufacturer.

SPECIFICATIONS

DISPOSABLE PANEL FILTERS

INTERNAL WIRE FRAME TYPE

UL CLASS I & II

1. SCOPE

This specification covers the Four Ply multi-graduated panel and link filters that are used as prefilters and final filters in air-conditioning, heating and ventilation systems.

2. PURPOSE

This specification is written to establish performance criteria, and to identify physical properties of the Four Ply PANELS AND LINKS that are pertinent and necessary for proper filter performance.

3. PERFORMANCE CRITERIA

3.1 The manufacturer shall have a representative sample of the product requested in the bid solicitation tested by an independent, commercially operated test laboratory approved by the purchaser. The independent test laboratory shall fully test one (1) representative filter purchased from the open market to ASHRAE Standard 52.2 P (Showing MER values),

Note: An equivalent 52.1 or 52-76 test showing equal to or greater than fractional efficiencies as in section 3.2.2 will be accepted, these particle penetration numbers must be provided by an independent laboratory and product must be purchased from the open market with no exception. The test must represent current production.

3.2 The resulting performance data shall be used to meet the following (3.2.2) Performance Requirements.

3.2.1

Nominal Filter Size 24 x 24 x 2

3.2.2

Performance Requirements

Maximum Initial Resistance 984 CFM .19” W.G.

1476 CFM .34” W.G.

1968 CFM .51” W.G.

2460 CFM .72” W.G.

Minimum Fractional Efficiencies .35um 6%

.55um 6%

.84um 10%

1.14um 23%

1.44um 62%

1.88um 80%

2.57um 89%

3.46um 93%

4.69um 93%

6.2um 94%

8.37um 94%

Final Resistance 1.0” W.G.

Minimum Efficiency Rating MER 11

4. BID ENCLOSURES

The following items must be part of the bid proposal. Failure to comply will cause

rejection of bids without recourse.

4.1 One (1) independent laboratory test report showing performance results when

tested to ASHRAE Standard 52.2 including particle size efficiency. The product must be purchased from the open market. The bidder to verbally verify the performance results with the independent laboratory that performed the test shall grant permission.

4.2 A product sample.

5. PHYSICAL CHARACTERISTICS

Four Ply panel and link filters are constructed of 4 distinct layers of pre-crimped, multi-graduated denier fibers, permanently bonded together during manufacture to provide progressive filtration; large particles are strained from the air stream on the air entering side and progressively smaller particles throughout successive ply’s. The pre-crimped fibers employed in the Four Ply forms millions of interstice funnel shaped traps to arrest and permanently retain, in depth, solid particulate materials in proportion to their micron size, without interrupting uniform air flow.

At manufacture, the first 3 ply’s of the Four Ply’s are permanently bonded together thereby providing a progressive density product in a single fabric. Individual ply’s laminated together are not acceptable, as mechanical bonding adversely affects air flow resistance, and shortens filter life. A wet tackifier must be applied between the last two plys of media to assist in retaining particles captured by the fibers. The tackifier must be non-toxic, Non-allergenic material and, applied to the media at the time of manufacture.

Each panel or link shall have an inner hard-drawn wire frame, heat-sealed between the two ply's; with cross braces as necessary. After heat sealing, each panel or link shall have a minimum of 1/2” selvage edge guaranteeing positive seal around the periphery of the filter.

Panels are available with AEGIS, antimicrobial agent.

Four Ply panels and links are UL Class I and UL Class II listed and approved per UL Standard 900.

*These filters must NOT contain any dyes or tinting of media*

* Each synthetic panel type filter must be labeled as to the downstream side to assure proper installation.

*Each panel filter must be labeled downstream side* To insure proper installation

6. PACKAGING AND IDENTIFICATION

6.1 Shipping containers shall be marked with the following:

6.1.1 The name or trademark of the product.

6.1.2 The nominal size of the filter.

6.1.3 Name of manufacturer.

................
................