YARWAY REPAIRABLE DRIP AND TRACER STEAM TRAPS SERIES 751/761
YARWAY REPAIRABLE DRIP AND TRACER STEAM TRAPS SERIES 751/761
Thermostatic steam traps that provide consistent performance in less than perfect conditions.
FEATURES
Thermostatic Traps ? Repairable ? Pressure assisted fail-open design ? Freeze proof ? Energy efficient subcooled discharge ? Hardened stainless steel valve body and seat ? Installation in any position ? Withstand superheat ? Operates against 99% back pressure ? Self draining (vertical mount) ? Easy to check ? Multiple subcool options ? Integral strainer option
751
761
GENERAL APPLICATION
The series 751/761 Unibody Plus bellows trap is designed for light load applications such as steam tracing, drip, and light process.
TECHNICAL DATA
Technology: Size:
Connections: Materials:
Thermostatic ", ?", ?", 1" (DN 10, 15, 19, 25) Threaded, Socket Weld low carbon (0.15% max.) chrome moly body and stainless steel trim
751/761 -5 & -40 Design: Operating: Max Temperature: Capacity: Back Pressure:
ANSI Class 600 1-300 psi (0.07 - 21 bar) 750?F (400?C) up to 675 lb/hr (306 kg/hr) 99%
751/761 -HP Design: Operating Pressure: Max Temperature: Capacity: Back Pressure:
ANSI Class 600
1-600 psi (0.07 - 41 bar) 750?F (400?C) up to 900 lb/hr (409 kg/hr) 99%
? 2020 Emerson. All Rights Reserved.
VCTDS-15699-EN 20/09
STESAtMeaTRmATPrFaLpOFlWoRwATRE,atKe,G/kHg/Rhr
YARWAY REPAIRABLE DRIP AND TRACER STEAM TRAPS SERIES 751/761
SERIES 751/761 THERMOSTATIC TRAPS (BELLOWS)
The series 751/761 is available in two body designs and with three Filled Thermal Elements (FTEs). The series 761 is an in-line body with an integral wye strainer and blowdown valve. The series 751 is an in-line body only. The FTEs to 300 psi are the -5 for drip tracing and light process; the -40 for tracing. The -HP is for applications to 600 psi. The FTEs are available in factory set and assembled renewal kits.
All internals are energy efficient. The -5 and -HP internals are slightly subcooled operating near steam temperature. The -40 internals operate 35?F to 45?F subcooled. The -HP is recommended for optimum service life limited to 450 psig.
Applicable codes and standards Pressure ratings per ANSI/FCI-69-1 Performance testing per ANSI/ASME PTC-39.1 End connections per ANSI B1.20.1 for threaded ends, per ANSI B16.11 for socket-welding ends.
CAPACITIES (FOR STEAM TRAP SIZING)
STEASMteTaRmAPTDrIaFpFEInRlEeNt TPIrAeLsPsRuEreS,SbUaRrE, bar
0.1 4000
0.2 0.3 0.5
1
23
5
10
20 30
STSEtAeaM TmRTArPapFLFlOoWwRARTatE,e,LlBb//HhRr
3000 2000
HP 1000
700
1000 800 700 600 500 400
300
500
300
CCOoLlDd
200
HoHt OT
200
100 80 70 1
751-5, 761-5 751-40, 761-40
100 70 751-HP, 50 761-HP
2 3 4 5 6 7 8 10
20 30 40 50 60 80 100 200 300 400 600
STEAMStTeRaAmPTDrIaFpFEInRlEeNtTPIAreLsPsRuErSeS, UpRsiE, PSI
FUNCTIONAL SUPERHEAT DESIGN LIMITS
OPERATING PRESSURE, bar 3.4 6.8 10.3 13.7 17.2 20.6 24.1 27.5 31.0 34.4 37.9 41.4
OPERATING TEMPERATURE, ?F
900
482
HOW TO SPECIFY AND ORDER
Typical specification - traps shall be
800
HP internals 5 Internals
426
thermostatic rated to 600 psi and actuated by
40 internals
a FTE stainless steel. The body shall be low
700
371
carbon (0.15 max c) chrome-moly steel with
threaded (socket-welding) end connections.
600
315
Trap shall be in-line repairable energy efficient thermostatic valve. Specify end connections to be threaded or socket-welded. Trap shall have replaceable capsule.
Ordering - specify trap pipe size, series number, FTE rating, and the type of end connections desired (threaded or socketwelding). The renewal capsule consists of a factory-calibrated FTE cage assembly, seat and bonnet, with seat gasket. Order by specifying: Renewal capsule for series 751/761 trap.
500
260
400
Saturation curve
204
300
149
200 0
93.3 50 100 150 200 250 300 350 400 450 500 550 600
OPERATING PRESSURE, PSIG
HOW TO SIZE
1. Determine maximum temperature and pressure of application and verify with trap. 2. Determine operating conditions Temperature, Inlet Pressure, Outlet Pressure, and Condensate Load (including factor of safety). 3. Determine the condensate load at the operating differential pressure is below what trap can handle. 4. Verify trap can handle back pressures
PRESSURE/TEMPERATURE RATINGS
Shell rating Max. design Temperature Max. operating Pressure Min. operating Pressure Operating temperature
751/761-5, -40 600 psi
750?F (400?C) 300 psi (21 bar) 1 psi (0.07 bar)
See chart
751/761-HP 600 psi
750?F (400?C) 600 psi (41 bar) 1 psi (0.07 bar)
OPERATING TEMPERATURE, ?C
2
YARWAY REPAIRABLE DRIP AND TRACER STEAM TRAPS SERIES 751/761
SERIES 751/761 THERMOSTATIC TRAPS (BELLOWS)
SERIES 751 3
B HEX
SERIES 761 A
B HEX
4
D Min. to
5
assemble
C 2
1
3 K thread size
4
D Min. to
assemble
5
C 2
1
6 7
13
14
Assembly with plugged strainer cap
Flow
K thread size A
GH
Socketweld end connections
Flow
6
7 8 9 10 11 12
PARTS AND MATERIALS
Item Part
1
Body
2[1]
Seat gasket
3[1]
Nameplate
4[1]
FTE cage assembly
5[1]
Bonnet
6
Screen
7[2]
Cap gasket
8[2]
Blowdown seat
9[2]
Retaining ring
10[2] Blowdown body
11[2] O-ring
12[2] Blowdown valve
13[3] Strainer cap
14[3] Plug NPT
15[3] Blank strainer cap
Materials ASME SA-182 GR. F11 low carbon, 0.15 max C Clad non-asbestos Stainless steel Stainless steel Stainless steel Stainless steel Monel? Stainless steel Stainless steel Stainless steel Silicone Stainless steel Stainless steel Carbon steel Stainless steel
E F Min. to
disassemble
J HEX
6 7
15 Assembly with blank
strainer cap
NOTES 1. Part of factory assembled assembled renewal capsule. 2. Factory assembled blowdown valve renewal kit. 3. Optional strainer caps.
DIMENSIONS AND WEIGHTS
Trap size in. (DN) (10) ? (15) ? (20) 1 (25)
A 35/32 (80) 35/32 (80) 335/64 (90) 315/16 (100)
B 1? (38) 1? (38) 1? (38) 1? (38)
C 23/16 (56) 23/16 (56) 2? (57) 2? (57)
Nominal dimensions, in. (mm)
D
E
F
G
3 (76) 2 (73) 315/16(100) (9.5)
3 (76) 2 (73) 315/16(100) (9.5)
31/16 (78) 3? (83) 415/16 (110) ? (12.7)
31/16 (78) 3 (86) 47/16 (113) ? (12.7)
H 0.695 (17.6) 0.860 (21.8) 1.070 (27.2) 1.335 (33.9)
J 11/16 (27) 11/16 (27) 13/16 (30) 13/16 (30)
K NPT ? NPT ? NPT 1 NPT
Weight lb. (kg)
Series 751
Series 761
2 (0.9)
2? (1.3)
2 (0.9)
2? (1.3)
2? (1.2)
3? (1.5)
2? (1.3)
4 (1.8)
3
VCTDS-15699 ? 2020 Emerson Electric Co. All rights reserved 09/20. Yarway is a mark owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co. The Emerson logo is a trademark and service mark of Emerson Electric Co. All other marks are the property of their prospective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such products at any time without notice.
Emerson Electric Co. does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any Emerson Electric Co. product remains solely with the purchaser.
4
................
................
In order to avoid copyright disputes, this page is only a partial summary.
To fulfill the demand for quickly locating and searching documents.
It is intelligent file search solution for home and business.
Related download
- spfeci ications
- yarway repairable drip and tracer steam traps series 751 761
- general assembly rsce
- subpart m pipeline sampling 761 240 761 257
- technical data sheet p2200su 761 akrx24 ep2
- lincolnweld l 61 lincoln electric
- adt761 series automated pressure calibrator additel
- 1 2 3 4 5 bs cg20 761 250 55 27 761 250 oo 18 jt
- aggregated life rbc and annual statement data 727 750 761
- printed in the united states of america nrel
Related searches
- repairable pickup trucks for sale
- john hopkins free tracer course
- installing a steam game outside steam folder
- cdc covid tracer jobs
- propofol drip protocol and er
- joint commission tracer portal
- joint commission tracer observation form
- post nasal drip and wheezing
- post nasal drip and bronchitis
- nicardipine iv drip and heart rate
- cat traps for tnr
- heparin drip policies and procedures