Data sheet (template) - Cummins

[Pages:3]Generator set data sheet

Model: Frequency: Fuel type: kW rating:

C1100 D5 50 Hz Diesel 1000 Data Center Continuous (DCC)

Spec sheet: Noise data sheet (open/enclosed): Cooling system data:

SS14-CPGK-DC50 ND50-OSHHP/ND50-CS550 MCP-1038

Fuel consumption

Ratings Load US gph L/hr

kVA (kW)

1000 (800)

1/4

1/2

14.2

26.9

54

102

Engine

Engine manufacturer Engine model Configuration Aspiration Gross engine power output, kWm BMEP at set rated load, kPa Bore, mm Stroke, mm Rated speed, rpm Piston speed, m/s Compression ratio Lube oil capacity, L Overspeed limit, rpm Regenerative power, kW Governor type Starting voltage

Fuel flow

Maximum fuel flow, L/hr Maximum fuel inlet restriction, mm Hg Maximum fuel inlet temperature, ?C

3/4

Full

39.8

53.2

151

202

Cummins QST30-G4 Cast iron, 50? V12 cylinder Turbocharged and charge air-cooled 880 2310 140 165 1500 8.3 14:1 133 1725 ?50 58 Electronic 24 Volts DC

550 203 71

?2017 Cummins Inc. | DS38-CPGK-DC (08/17)

power.

Air

Combustion air, m3/min

Maximum air cleaner restriction, kPa

56.70 6.2

Exhaust

Exhaust gas flow at set rated load, m3/min

165

Exhaust gas temperature, ?C

565

Maximum exhaust back pressure, kPa

6.8

Standard set-mounted radiator cooling

Ambient design, ?C Fan load, kWm Coolant capacity (with radiator), L Cooling system air flow, m3/sec @ 12.7 mm H2O Total heat rejection, Btu/min Maximum cooling air flow static restriction mm H2O

40 27 192 12.6 26390 12.7

Weights*

Open

Enclosed

Unit dry weight, kgs

7416

N/A

Unit wet weight, kgs

7621

N/A

* Weights represent a set with standard features. See outline drawing for weights of other configurations.

Dimensions

Standard open set dimensions, mm Enclosed set standard dimensions, mm

Length 4417 N/A

Width 2000 N/A

Genset outline

Open set

Height 2387 N/A

?2017 Cummins Inc. | DS38-CPGK-DC (08/17)

power.

Alternator data

Connection

Wye, 3-phase

Temp rise ?C 150/125

Duty DCC

Alternator HC6K

Voltage 380-440

Ratings definitions

Data Center Continuous (DCC):

Applicable for supplying power continuously to a constant electrical load for unlimited hours in a data center application where a reliable utility is present. The Data Center Continuous (DCC) power rating is in accordance with ISO8528.

Formulas for calculating full load currents:

Three phase output

kW x 1000 Voltage x 1.73 x 0.8

For more information contact your local Cummins distributor or visit power.

?2017 Cummins Inc. All rights reserved. Cummins is a registered trademark of Cummins Inc. PowerCommand, AmpSentry, InPower and "Our energy working for you." are trademarks of Cummins Inc. Other company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice. DS38-CPGK-DC (08/17)

................
................