The MA-15S motor actuator is easy to install, easy to wire up, and comes with a 5 year warranty. The superior design insures long life and zero maintenance. The Motor can be oriented in any position in a conditioned area. The UL Listed Motor Actuator is a 24vac 3 wire power open & power close type rated at 18 inch lbs. of torque and 15 second travel time. The MA-15S can also operate in floating mode and is compatible with Carrier? Infinity & Bryant? Evolution communicating zone control systems. The MA-15S includes an integrated wiring terminal block, and has a NEMA1 rated housing. Dual End-Stop adjustments allow for a maximum Open and Minimum Close field position capability.
Technical Data
Power Supply
24 VAC ? 20% 50/60Hz
24 VDC ? 10%
Power Consumption 1.5 W
Transformer Sizing 2.5 VA (Class 2 power source)
Electrical Connection Screw Terminal
(26 to 14 GA Wire)
Control Function
Open / Close or Floating Point
Torque
18 in-lb [2 Nm]
Manual Override
External Push Button
Running Time
15 seconds, constant
independent of load
Humidity
5 to 95% RH Non-Condensing
Ambient Temperature -22?F to +122?F
[-30?C to +50?C]
Storage Temperature -40?F to +176?F
[-40?C to +80?C]
Housing
NEMA 1 / IP20
Housing Material UL94-5VA
Agency Listings
cULus
Noise Level
45dB(A)
END STOP ADJUSTMENT
-LOOSEN PHILIPS HEAD SCREW -MOVE END-STOP TO DESIRED "CLOSED" POSITION -TIGHTEN PHILIPS HEAD SCREW
0
1
0
1
Excellence Without Comprimise
EwC
CONTROLS INC.
MA-15S
18 in-lb / 2Nm 24VAC/DC 15s 2.5VA 1.5W
III !
C UL US
1
4
6
2.75" A
B
NOMINAL DIMENSIONS
MODEL # A
B .1" WC
URD - 4 URD - 5 URD - 6 URD - 7 URD - 8 URD - 9 URD - 10 URD - 12 URD - 14 URD - 16 URD - 18 URD - 20
4.00" 10.00" 40 CFM 5.00" 10.00" 70 CFM 6.00" 12.00" 110 CFM 7.00" 12.00" 160 CFM 8.00" 12.00" 230 CFM 9.00" 12.00" 310 CFM 10.00" 12.00" 410 CFM 12.00" 14.00" 650 CFM 14.00" 16.00" 1000 CFM 16.00" 20.00" 1400 CFM 18.00" 20.00" 2000 CFM 20.00" 20.00" 2500 CFM
Excellence Without Compromise
EWC
CONTROLS INC.
385 Hwy. 33 Englishtown, NJ 07726 Ph: 800-446-3110 Fx: 732-446-5362
SUBMITTAL FORM SUBMITTED BY: JOB: ARCHITECT: ENGINEER: CONTRACTOR: LOCATION:
P/N 090377A0069 REV. B 1.11.18 Copyright ? 2006 EWC Controls Inc., All Rights Reserved.
? Forced Air Zone Controls
SUBMITTAL SHEET Model URD Round Damper
with MA-ND5 Actuator
WIRING SOLUTIONS
Motor Actuator Terminals
TERMINAL 1 4 6
DESCRIPTION 24v Com.
Power Open Power Close
Wiring to a Zone Control Panel
MA-15s ACTUATOR
ZONE CONTROL DAMPER OUTPUT
6
M6 / PC
4
M4 / PO
1
M2/HOT
M1/COM
Wiring a Thermostat to Control a Single Damper
MA-15S COM 1 PO 4 PC 6
JUMPER
MODEL
T40-VA
C
TO
R
PRIMARY
24VAC 40VA TRANSFORMER
OR EQUIVELENT
Y WR G
EWT THERMOSTAT
1 HEAT / 1 COOL OR
EQUIVALENT
Wiring in Parallel
ZONE CONTROL DAMPER OUTPUT
M6 M4 M2 M1
MA-15s
6 4 1
MA-15s
6 4 1
MA-15s
6 4 1
NOTE: You may electrically parallel several MA-15S motors together on a single zone. However, DO NOT parallel the MA-15S with original Carrier/Bryant damper motors on the same zone. The back-feed characteristic of the Carrier/Bryant motors is not compatible with the MA-15S motors.
Excellence Without Compromise
EWC
CONTROLS INC.
385 Hwy. 33 Englishtown, NJ 07726 Ph: 800-446-3110 - Fx: 732-446-5362
P/N 090377A0069 REV. B 1.11.18 Copyright ? 2006 EWC Controls Inc., All Rights Reserved.
................
................
In order to avoid copyright disputes, this page is only a partial summary.
To fulfill the demand for quickly locating and searching documents.
It is intelligent file search solution for home and business.
Related download
- model urd round dampers forced air zone controls
- submittal sheet model urd round damper forced air zone ewc
- rsd forced air zone controls round spring return damper
- model urd round dampers forced air zone controls southern pipe
- model urd round damper forced air zone controls with ma ewc
- model prd rd barometric bypass damper ewc
Related searches
- concentric zone model aphg
- model 995 9mm 20 round magazine redball
- zone damper system
- hvac zone damper motor
- hvac zone damper system cost
- replace hvac zone damper control
- residential hvac zone damper systems
- air conditioning damper cost
- air conditioning damper problems
- carrier zone damper system
- honeywell zone damper motor replacement
- carrier damper motor model 175