RSD Forced Air Zone Controls Round Spring-Return Damper
Forced Air Zone Controls
SUBMITTAL SHEET
Model RSD Round Spring-Return Damper
Model RSD is a round single blade damper constructed from heavy (24) gauge galvanized steel. The 24 volt motor actuator is direct coupled to the drive shaft. It is a power closed/spring open action. (standard). The damper can be field reversed to a power open/spring closed action. The RSD has a double layered blade design with an integrated Poron? foam gasket to provide a seal when the damper is in the closed position. The RSD also has a Travel Limiter to prevent the damper from closing 100% if your application requires. Note: 18" and 20" RSD models utilize a Belimo TF series actuator for increased reliability. The hysteresis motor can get very warm when energized/stalled for extended time periods. To avoid overheating, DO NOT cover/encapsulate or insulate the motor housing. Doing so will damage the actuator assembly.
DIMENSIONS
TRAVEL LIMIT
3.04"
50% 75% 100%
MODEL # A
B
RSD-4
4.0" 12.00"
RSD-5
5.0" 12.00"
RSD-6
6.0" 12.00"
RSD-8
8.0" 12.00"
A
RSD-10
10.0" 12.00"
RSD-12
12.0" 14.00"
RSD-14
14.0" 16.00"
RSD-16
16.0" 20.00"
RSD-18
18.0" 20.00"
RSD-20
20.0" 20.00"
B
TRAVEL LIMIT ADJUSTMENT
RSD
14"
EWC
CONTROLS INC. 385 HIGHWAY 33, ENGLISHTOWN, NJ 07726
(732) 446-3110 * FAX: (732) 446-5362
TRAVEL LIMIT
50% 75% 100%
INC.
MODEL
MA-RSD
MOTOR CONRETVR. AOLS,
TM
E WC
CAUTION
Do not operate
Damper manually,
doing so may
damage motor
EWC Controls, Inc. 385 Highway 33
Englishtown, N.J. 07726 1-800-446-3110
-LOOSEN BOLT -SLIDE BOLT TO DESIRED LOCATION -TIGHTEN BOLT
Excellence Without Compromise
EWC
CONTROLS INC.
385 Hwy. 33 Englishtown, NJ 07726 Ph: 800-446-3110 - Fx: 732-446-5362
P/N 090377A0123 REV. F Copyright ? EWC Controls 2006-2007 All Rights Reserved
Forced Air Zone Controls
To Field Reverse Motor:
1) Remove Button Head screw securing the Motor shaft to the Damper blade shaft.
2) Remove Anti-Rotation Nut on bottom of Motor Actuator.
3) Remove Motor Actuator from damper. 4) Rotate damper blade 90? 5) Mount motor onto damper blade shaft
180? opposite of original location. 6) Re-insert Anti-Rotation nut and Button
Head screw and tighten. 7) Wire & Power up motor to insure
TRAVEL LIMIT 50% 75% 100%
SUBMITTAL SHEET
Model RSD Round Spring-Return Damper
BUTTON-HEAD SET SCREW
(Located underneath Motor Actuator)
POWER CLOSE
SIDE
POWER OPEN SIDE
ANTI-ROTATION NUT
WIRING SOLUTIONS
MOTOR Terminal Output
M6 - power to close M4 - power to open M2 - constant power M1 - common
Wiring to a Control Panel
MODEL RSD
ZONE PANEL
Motor
M6
* M4
M2
M1
*DAMPER SHOWN AS POWER CLOSE/SPRING OPEN IF FIELD CONFIGURED AS POWER OPEN/SPRING CLOSE WIRE TO M4 TERMINAL.
Wiring a Thermostat to Control a Single Damper
H C
TRANSFORMER 24VAC, T-40VA
or EQUIVALENT
Motor
* MODEL RSD
FAN AUTO ON
SYSTEM COOL OFF HEAT
Conventional Thermostat
WYR G
EWT THERMOSTAT w/TSB-M SUB-BASE
or EQUIVALENT
*DAMPER SHOWN FIELD CONFIGURED AS POWER OPEN/SPRING CLOSE. IF POWER CLOSE/SPRING OPEN, DAMPER MUST BE FIELD REVERSE, IF POSSIBLE.
Excellence Without Compromise
EWC
CONTROLS INC.
385 Hwy. 33 Englishtown, NJ 07726 Ph: 800-446-3110 - Fx: 732-446-5362
P/N 090377A0123 REV. F Copyright ? EWC Controls 2006-2007 All Rights Reserved
................
................
In order to avoid copyright disputes, this page is only a partial summary.
To fulfill the demand for quickly locating and searching documents.
It is intelligent file search solution for home and business.
Related download
- model urd round dampers forced air zone controls
- submittal sheet model urd round damper forced air zone ewc
- rsd forced air zone controls round spring return damper
- model urd round dampers forced air zone controls southern pipe
- model urd round damper forced air zone controls with ma ewc
- model prd rd barometric bypass damper ewc
Related searches
- doppler penile ultrasound forced ejaculation
- what is forced annuitization
- return air cfm calculator
- zone damper system
- hvac zone damper motor
- hvac zone damper system cost
- replace hvac zone damper control
- residential hvac zone damper systems
- air conditioning damper cost
- air conditioning damper problems
- carrier zone damper system
- honeywell zone damper motor replacement