Tandem Combination Type Arc-Fault Circuit Interrupters (CAFCI)

[Pages:8]Tandem Combination Type Arc-Fault Circuit Interrupters (CAFCI)

Pigtail and Plug-On Neutral

Pigtail Plug-On Neutral

Siemens Tandem AFCI Breakers are the perfect solution to wiring made easier. The design allows for more circuits in a smaller loadcenter. Installed indicator flags disappear when the load wires are inserted correctly.

Siemens CAFCI Plug-On breakers now have a single load lug(s) only. Wiring made easier with the neutral lug removed. These breakers can be installed in the same manner as the thermal magnetic breakers. This allows the installer to land ground and neutral conductors in the load center before installing the breaker and load conductor.

Tandem AFCI breakers without the rejection feature can be installed in any panel that lists that breaker type or where a substitution letter exists for that breaker type. The schematic, located on the wiring diagram, will indicate the positions where these breakers can be placed by showing two circuits per space. The total circuits listed for panel should not be exceeded.

Catalog Number Q1515AFC Q2020AFC Q1515AFCN Q2020AFCN

Ampere Rating 15/15 20/20 15/15 20/20

Interrupting Rating

10kA

UL Type

QTA

10kA

QTA

10kA

QTAN

10kA

QTAN

Connection Type Pigtail Pigtail Plug-On Neutral Plug-On Neutral

Features

? One breaker feeds two circuits to save on space and time ? Installed indicator flags disappear when the load wires are

inserted correctly ? Load Lug(s) only ? Available in pigtail and Plug-On neutral types ? Trusted Plug-On Neutral connection ? LED indicators for troubleshooting ? Insta-wire connectors

Technical Data

? 10,000 AIC ? 120V ? UL Listed ? HACR and SWD rated

usa.afci

N

Ground Wire D

Wiring Diagrams

Neutral S/N GND

Ground Wire

Pigtail

120V AC LINE

N A/B

120 Plug-On Neutral Terminal must be connected to panel neutral.

120V AC LINE N A/B

120

Plug-On Neutral Terminal must be connected to panel neutral.

al

1-Pole AFCI eutral

1x20V AC LOADS

Ground Wire

TWIN

Neutral

S/N

Plug-On Neutral

x120V AC x LOADS

1x20V AC LOADS

GND

S/N GND

Grou1n-dPoWleire DF or GFCI

Ground Wire

Plug-On Neutral

120V AC LINE

N A/B

120

Plug-On Neutral Terminal must be connected to panel neutral.

Plug-On Neutral

TWIN

Neutral S/N GND

Ground Wire

x120V AC x LOADS

120//208/240V A LINE

NB A 120 120

208V 240V

Plug-On Neu

S/N

GN

2

Dimension Diagrams

Pigtail

Plug-On Neutral

3

Time Current Characteristic Curve ? 15A

SIEMENS

15 A

Time Current Characteristic Curve

AFCI Frame, Types QTA, QTAN Thermal Magnetic Tandem Circuit Breaker

For coordination purposes only. Based on 40?C ambient cold start. Connected with 4 feet of rated wire (75?C) per terminal. Tested in open air with current.

Types QTA, QTAN 60Hz 120 Volts

Instantaneous Trip Table

Rating Amperes

Fixed Instantaneous Trip Amperes

15 - 20

200 - 350

Interruption Ratings

Breaker Type

Symetrical RMS Amperes 120 Volt

QTA, QTAN

10 kA

Time in Seconds

R815494 15A CAFCI REV. 0 SHEET 1 OF 2 - FEBRUARY 2021

4

For Max. Interruption Rating See table above.

Current in Amperes

Siemens Industry Inc. Norcross, GA, 30092

Time Current Characteristic Curve ? 20A

SIEMENS

20 A

Time Current Characteristic Curve

AFCI Frame, Types QTA, QTAN Thermal Magnetic Tandem Circuit Breaker

For coordination purposes only. Based on 40?C ambient cold start. Connected with 4 feet of rated wire (75?C) per terminal. Tested in open air with current.

Types QTA, QTAN 60Hz 120 Volts

Instantaneous Trip Table

Rating Amperes

Fixed Instantaneous Trip Amperes

15 - 20

200 - 350

Interruption Ratings

Breaker Type

Symetrical RMS Amperes 120 Volt

QTA, QTAN

10 kA

Time in Seconds

R815494 20A CAFCI REV. 0 SHEET 2 OF 2 - FEBRUARY 2021

For Max. Interruption Rating See table above.

Current in Amperes

Siemens Industry Inc. Norcross, GA, 30092

5

Notes:

6

Notes:

7

Published by Siemens 2021

Siemens Industry, Inc. 3617 Parkway Ln Peachtree Corners, GA 30092

Siemens Technical Support: 1-800-333-7421 info.us@

Order No. RPDS-CAFCI-0421 Printed in USA All Rights Reserved ? 2021, Siemens Industry, Inc. usa.afci

The technical data presented in this document is based on an actual case or on as-designed parameters, and therefore should not be relied upon for any specific application and does not constitute a performance guarantee for any projects. Actual results are dependent on variable conditions. Accordingly, Siemens does not make representations, warranties, or assurances as to the accuracy, currency or completeness of the content contained herein. If requested, we will provide specific technical data or specifications with respect to any customer's particular applications. Our company is constantly involved in engineering and development. For that reason, we reserve the right to modify, at any time, the technology and product specifications contained herein.

................
................

In order to avoid copyright disputes, this page is only a partial summary.

Google Online Preview   Download